3412C | 750kVA

3412C | 750kVA

Caterpillar is leading the power generation marketplace with Power Solutions engineered to deliver unmatched flexibility, expandability, reliability, and cost-effectiveness.

Maximum Rating 680 kVA 680 kVA
Minimum Rating 680 kVA 680 kVA
Emissions/Fuel Strategy Low Fuel Consumption Low Fuel Consumption

ტექნიკური მახასიათებლები

Generator Set Specifications
Maximum Rating 680 kVA 680 kVA
Minimum Rating 680 kVA 680 kVA
Emissions/Fuel Strategy Low Fuel Consumption Low Fuel Consumption
Voltage 380 to 415 Volts 380 to 415 Volts
Frequency 50 Hz 50 Hz
Speed 1500 rpm 1500 rpm
Duty Cycle Standby, Prime Standby, Prime
Engine Specifications
Engine Model 3412C TA, V-12, 4-Stroke Water-Cooled Diesel 3412C TA, V-12, 4-Stroke Water-Cooled Diesel
Bore 5.4 in 137.2 mm
Stroke 6 in 152.4 mm
Displacement 1648.86 in³ 27.02 l
Compression Ratio 13:01 13:01
Aspiration Turbocharged, Air to Air Aftercooled Turbocharged, Air to Air Aftercooled
Fuel System Pump and Lines Pump and Lines
Governor Type ADEM™ A5 ADEM™ A5
Generator Set Dimensions
Length - Maximum 162.4 in 4125 mm
Width - Minimum 75 in 1906 mm
Width - Maximum 78.3 in 1989 mm
Height - Maximum 75 in 1906 mm
Dry Weight - Genset (minimum) 12039 lb 5461 kg
Dry Weight - Genset (maximum) 13030 lb 5910 kg

უპირატესობები და მახასიათებლები

Cat Generator Set Package

  • Cat generator set packages have been fully prototype tested
  • Accepts 100% block load in one step and meets NFPA 110 loading requirements
  • Conform to ISO 8528-5 steady state and transient response requirements

Cat Diesel Engine

  • Reliable, rugged, durable design
  • Field-proven in thousands of applications worldwide
  • Four-stroke-cycle diesel engine combines consistent performance and excellent fuel economy with minimum weight

SR500 Alternator

  • Superior motor starting capability minimizes need for oversizing alternator
  • Designed to match performance and output characteristics of Cat diesel engines
  • Robust Class H insulation

EMCP 4 Control Panel

  • User-friendly interface and navigation
  • Scalable system to meet a wide range of installation requirement
  • Expansion modules and site-specific programming for specific customer requirements

Cooling System

  • Designed to operate in standard ambient temperatures up to 50°C (122°F)
  • Contact your Cat Dealer for specific ambient and altitude capabilities

Certifications

  • EU Declaration of Conformity
  • EU Declaration of Incorporation
  • Eurasian Conformity (EAC)

One Safe Source

  • Components used in the generator set are selected based on seamless design integration to provide the optimum performance
  • The generator set is fully assembled at a Caterpillar facility following our quality guidelines
  • Each generator set package is tested before leaving the Caterpillar facility
  • Cat product support, including dealer service, parts and warranty covers the entire Cat power system

World Wide Product Support

  • Cat dealers have over 1,800 dealer branch stores operating in 200 countries
  • Your local Cat dealer provides extensive post-sale support, including maintenance and repair agreements

სტანდარტული ტექნიკა

  • Air Inlet System
    • Air cleaner, single element canister type with service indicator
  • Control Panel
    • EMCP 4.2B
    • Over/under voltage (27 / 59)
    • Environmental sealed front face
    • Generator phase sequence
    • Communications
    • Digital I/O module
    • Features include:
    • 2 Programmable relay outputs (Form C)
    • Compatible with the following optional modules:
    • Customer data link (Modbus RTU)
    • 4 programmable relay outputs (Form A)
    • Amps (per phase & average)
    • kVA (per phase, average & percent)
    • Text alarm/event descriptions
    • Low coolant level
    • Generator temperature monitoring module
    • Run/auto/ stop/control
    • Overspeed
    • Serial annunciator module data link
    • Emergency stop pushbutton
    • Frequency (Hz)
    • RPM
    • 6 programmable digital inputs
    • Oil pressure (psi, kPa or bar)
    • Engine cycle crank
    • Operating hours
    • Local annunciator
    • coolant temperature
    • kW-hr (total)
    • Programmable protective relaying functions:
    • kW (per phase, average & percent)
    • Low oil pressure
    • Reverse power (kW) (32)
    • Remote Serial annunciator
    • DC volts
    • Power factor (per phase & average)
    • Remote CAN annunciator
    • 24 Volt DC operation
    • Accessory module data link
    • Failure to start (overcrank)
    • Over/under frequency (81 o/u)
    • kVAr (per phase, average & percent)
    • Warning/shutdown with common LED indication of shutdowns for:
    • Low coolant temperature
    • 2 Programmable digital outputs
    • Reverse reactive power (kVAr) (32RV)
    • Emergency stop
    • Digital indication for:
    • High coolant temperature
    • Speed adjust
    • Voltage adjust
    • Volts (L-L & L-N)
    • Overcurrent (50 / 51)
  • Cooling System
    • Fan and belt guards
    • Coolant drain line with valve, piped to edge of base
    • Caterpillar extended life coolant
    • Coolant level shutdown
    • Radiator with guard (Sized for 50 degrees C)
  • Exhaust System
    • Stainless steel exhaust flex with ANSI style outlet flange, gasket, bolts and mating weld flange, shipped loose
  • Fuel System
    • Flexible fuel lines terminated on base
    • Fuel priming pump
    • Primary and Secondary fuel filters
    • Water seperator
  • Generator and Attachments
    • 3-phase sensing
    • SR4B self excited
    • Class H insulation
    • 2:1 Volts/Hz
    • Reactive droop
    • VR6 voltage regulator
    • Busbar termination
    • Class F temperature rise
    • 12 Leads
  • Governing System
    • Cat electronic governor
  • Lube System
    • Oil drain line with valve, piped to edge of base
    • Lubricating oil
    • Oil filter
    • Fumes disposal, piped to front of radiator
  • Mounting System
    • Base, formed steel with linear vibration isolators between base and engine-generator
  • Starting / Charging System
    • Battery with rack, cables
    • 45 amp Charging alternator
    • 24 volt starting motor
    • Fuel shutoff solenoid

აირჩიეთ ტექნიკა

  • Air Inlet System
    • Open element air cleaners
    • Heavy duty air cleaners
    • Dual element air cleaners
  • Circuit breakers
    • 1600 Amp, 3 pole, Non-UL, 100% rated, 24 volt DC shunt trip
    • 1250, 1600 Amp, 3 pole, IEC 100% rated, 24 volt DC shunt trip
  • Control Panel
    • First local annunicators
    • Local discrete I/O package
    • Generator temperature monitoring package
    • Ground fault relay
    • Remote custom annunicator
    • EMCP 4.3
    • Generator running VFC
    • EMCP 4.4
    • Vandal proof panel door
    • Common alarm/shutdown relay
  • Cooling System
    • Jacket water heaters
    • Radiator duct flange
  • European Certifications
    • Eurasian Conformity (EAC) mark
  • Exhaust System
    • Elbow kit
    • Manifold and turbocharger guards
    • Through wall installation kit
    • Mufflers
  • Generator and Attachments
    • Digital voltage regulator
    • Oversize and premium generators
    • Space heater
    • Permanent magnet excitation (PMG)
  • Lube System
    • Manual sump pump
  • Mounting System
    • Fuel tank base (1200 ltr)
  • Special Tests / Reports
    • PGS Test report @ 1.0 power factor
    • PGS Test report @ 0.8 power factor
  • Starting / Charging
    • Heavy duty starting system
    • Battery chargers
    • Battery disconnect switch
    • Oversize batteries
  • Governing System
    • Electronic load share