Technicial Specifications
| Continuous Rating | 1515 ekW / 1505 ekW @1.0pf 1515 ekW / 1505 ekW @1.0pf | 
| Fuel Type | Natural Gas, Hydrogen Blend (up to 25%) Natural Gas, Hydrogen Blend (up to 25%) | 
| Maximum Electrical Efficiency | 44.90% 44.90% | 
| Frequency | 50 / 60 Hz 50 / 60 Hz | 
| RPM | 1500 rpm 1500 rpm | 
| Engine Model | G3512H G3512H | 
| Displacement | 3574 in³ 59 l | 
| Aspiration | TA TA | 
| Bore | 6.7 in 170 mm | 
| Stroke | 8.5 in 215 mm | 
| Governor Type | ADEM A4 ADEM A4 | 
| Length | 223 in 5656 mm | 
| Width | 76 in 1921 mm | 
| Height | 91 in 2308 mm | 
| Dry Weight - Genset | 31085 lb 14100 kg | 
Advantages and Features
Cat G3512H Gas Engine
- Robust high speed block design provides prolonged life and lower owning operationg costs
- Designed for maximum performance on low pressure pipeline natural gas and hydrogen mixtures
- Simple open chamber combustion system for reliability and fuel flexibility
- Leading edge technology in ignition system and air/fuel ratio control for lower emission and engine efficiency
- One electronic control module handles all engine functions: ignition, governing, air/fuel ratio control and engine protection
SR5 Generator
- Designed to match performance and output characteristics of Caterpillar gas engines
- Industry leading mechanical and electrical design
- High efficiency
EMCP 4.3 Control Panel
- User-friendly interface and navigation
- Scalable system to meet a wide range of installation requirement
- Expansion modules and site-specific programming for specific customer requirements
Emissions
- Meets most worldwide emissions requirements down to 0.5 g/bhp-hr NOx level without aftertreatment
Proven System
- Field proven in a wide range of applications worldwide
- Fully prototype tested
- Certified torsional vibration analysis available
Full Range of Attachments
- Wide range of bolt-on system expansion attachments
- Factory designed and tested
- Flexible packaging options for easy and cost effective installation
Worldwide Product Support
- Cat dealers have over 1,800 dealer branch stores operating in 200 countries
- Your local Cat dealer provides extensive post-sale support, including maintenance and repair agreements
Standard Equipment
- 
                        Air Inlet
                        
                        - Package Mounted Air Cleaner with service indicator
 
- 
                        Cooling
                        
                        
                        - Jacket water and SCAC thermostats
 - 2nd Stage CAT Flange
 - ANSI Class 150 JW Connection
 - Engine driven pumps for jacket water and aftercooler cooling
 
- 
                        Control Panels
                        
                        - Dedicated customer wiring terminals
 
- 
                        Control Panel
                        
                        - EMCP4.3
 
- 
                        Exhaust
                        
                        
                        - Dry exhaust manifolds insulated and shielded
 - Center section cooled turbocharger with Cat flanged outlet
 
- 
                        Generator
                        
                        - High efficiency low voltage Cat generator, permanent magnet excitation, digital regulation, IP23 water ingress protection, & form wound construction.
 
- 
                        Starting/Charging
                        
                        - Electric Starter
 
- 
                        General
                        
                        
                        - Paint - Caterpillar Yellow except rails and radiators gloss black
 - Crankshaft vibration damper and guard
 
Optional Equipment
- 
                        Air Inlet
                        
                        
                        - Mounting brackets and piping
 - Air cleaner with precleaner
 
- 
                        Control Panels
                        
                        - Remote annunciator
 
- 
                        Circuit Breakers
                        
                        
                        - Frame mounting circuit breaker orientation
 - 2500A 3-pole IEC rated circuit breakers
 - Rear Mounted Circuit Breaker
 - 3000A/3200A/4000A UL100% Rated Masterpact circuit breaker (60 Hz only)
 - LSI Long-Time, LSI-P Long-Time, LSIG Long-Time, LSIG-P Long-Time,
 
- 
                        Control Panel
                        
                        
                        - Language Options
 - Cable Shroud Location
 - Engine failure relay
 - Discrete I/O module, 12 digital points, 8 'Form C' relay
 - 16 point/32 light annunciator with NFPA99-110/CSA282 configuration
 - Empty Upper Box Right/Left
 - Local Alarm module
 - Synchronization module
 - Cat Connect: Ethernet, satellite, or cell telematics
 - Local/Remote PC Monitorring
 - Right/Left/Rear Extension Box
 
- 
                        Cooling
                        
                        
                        - Remote radiator for JW and SCAC circuits
 - 220V (50Hz), 240V (60Hz), 480V (60Hz) JW heater
 
- 
                        Exhaust
                        
                        
                        - Flexible fitting [305mm x 305mm (12in. X 12in.)] w/ 12 bolt-flanges
 - 406mm (16in.) sparking-arresting muffler with companion flange
 - Exhaust expander [250mm-329mm (10in-12in)]
 - 305mm (12 in.) flange
 - Muffler options
 - Elbow exhaust
 
- 
                        Fuel System
                        
                        
                        - 1/2" NPT gas train conduit connectors
 - 3, 0-100kPag 4-20mA gas train pressure sensors
 - Fuel Filter
 - Gas knockdown regulators
 
- 
                        General
                        
                        
                        - Digital Diagnostic tool
 - US Aid emblem
 
- 
                        Generator
                        
                        
                        - Generator air filter
 - Manual voltage control
 - Cable access box
 - RTD Monitorring
 - Bearing temperature detectors
 
- 
                        Governing System
                        
                        - ADEM A4 4-20mA (0-5V) speed input
 
- 
                        Starting/Charging
                        
                        
                        - Battery with cables and rack
 - 24V Starting motors
 - 20A, 24VDC battery charger
 - 45A, 24V charging alternator (requires engine driven pumps)
 - Jacket water heater
 
- 
                        Grid Code Compliance
                        
                        
                        - 60 Hz: USA
 - 50 Hz: Germany, Great Britain, Belgium, Romania, Italy, Ireland, Poland, Netherlands, Spain, France, and European Standard
 